Catto / Topic Map · Electronic Technology Level 5
Electronic Technology · 120 h · Topic 6 of 9

Sensors for automation and control

A single gauge in a bridge mistakes 20 °C of heating for 100 microstrain. With two or four gauges in adjacent arms, the temperature cancels and the signal doubles or quadruples.

Proximity sensor Encoder Strain gauge Wheatstone bridge 4–20 mA loop

01Presence and position sensors

An automation system needs to know where the parts and mechanisms are. Presence sensors give a binary output; position sensors, a value:

SensorPrincipleDetects
Limit switchMechanical contactAny object that actuates it
InductiveAn oscillator loses energy through eddy currents in the targetMetals, at a few millimeters
CapacitiveThe object changes the capacitance of an electrodeAlmost any material, even liquids through a container
OpticalThrough-beam, reflection from a mirror or from the objectObjects at distances of meters
UltrasonicTime of flight of a pulseDistance, level, transparent objects
EncoderOptical or magnetic disk with marksAngular position and speed

Three-wire industrial sensors have a PNP output, which connects the load to the positive, or NPN, which connects it to ground; the one that matches the controller input has to be chosen. An incremental encoder delivers two channels in quadrature, A and B, which give the position by counting pulses and the direction by which one leads; it is lost when power is cut. An absolute encoder delivers a code, often Gray, that identifies each position.

02Temperature, force and pressure

Thermocouples generate a few microvolts per degree between two different metals, about 41 μV/K in type K, and need cold-junction temperature compensation. Platinum RTDs, such as the Pt100, have 100 Ω at 0 °C and a coefficient of 0.00385 per degree according to IEC 60751; they are connected with three or four wires so as not to measure the resistance of the cables. Force, weight and pressure are measured almost always with strain gauges: a metal trace on an insulating backing, bonded to the part, that changes resistance when it deforms:

\[ \frac{\Delta R}{R} = GF\,\varepsilon \] The gauge factor \( GF \) is about 2 in metallic gauges. A strain of 1000 μm/m, one part per thousand, changes the resistance by only 0.2 %: it has to be measured with a bridge.

03The strain-gauge bridge

In a Wheatstone bridge excited with \( V_{ex} \), one active gauge in one arm (quarter bridge) gives a nonlinear output and cannot tell strain from heating, because the gauge changes resistance with temperature. With two gauges in adjacent arms that deform in opposite directions, like the two faces of a beam in bending (half bridge), the output is doubled, linear, and the temperature effect cancels. With four (full bridge), it is quadrupled:

\[ V_o \approx k \, V_{ex}\,GF\,\varepsilon, \quad k = \tfrac14,\ \tfrac12,\ 1 \] Commercial load cells are full bridges and are specified in mV/V: one of 2 mV/V excited with 5 V gives 10 mV at full load. The conditioning of those signals was covered in sensor conditioning.
Lab · strain-gauge bridge

Gauges with GF = 2 in a bridge excited with 5 V, with an apparent thermal output of 5 μm/m per degree. The strain is measured by dividing the output by \( k V_{ex} GF \). The blue curve is the chosen configuration; the gray one, the ideal straight line.

04Industrial interfaces

The 4–20 mA current loop transmits an analog measurement over two wires for hundreds of meters: the current does not depend on the cable resistance, the same loop powers the transmitter, and the live zero of 4 mA makes it possible to detect a broken cable, which gives 0 mA. The HART protocol superimposes digital data on that loop. IO-Link (IEC 61131-9) connects sensors and actuators with point-to-point communication over the same three-wire cable, which makes it possible to configure and diagnose them. The connection of these sensors to controllers is covered in introduction to control and in the control subjects.

05In the lab

Activity 1 · Beam with strain gauges

Bond gauges on both faces of a cantilever beam, load it with known weights and compare quarter and half bridge, before and after heating it with air.

Activity 2 · Inductive sensor

Measure the switching distance of an inductive sensor with steel, aluminum and brass targets, and compare with the reduction factors in the datasheet.

Activity 3 · 4–20 mA loop

Build a loop with a transmitter, a 24 V supply and a 250 Ω resistor, and measure the voltage at the input for the whole range.

06Common mistakes

  • Measuring with a single gauge without compensation. Temperature shows up as strain.
  • Connecting a PNP sensor to an input that expects NPN. The input never sees the change.
  • Connecting a Pt100 with two wires over a long cable. The cable resistance adds as temperature.
  • Reading 0 mA as the bottom of the scale. In a 4–20 mA loop it is a broken cable.

07Self-assessment

What output does a full bridge give with GF = 2, 5 V and 1000 μm/m?

10 mV.

And a quarter bridge?

About 2.5 mV, slightly less because of the nonlinearity: 2.4975 mV.

Why does the half bridge compensate temperature?

The two gauges change equally with temperature and are in adjacent arms, where equal changes cancel.

What current corresponds to 50 % of the scale in a 4–20 mA loop?

12 mA.

08Further reading

  • Ramón Pallás Areny. Sensores y acondicionadores de señal. 4th ed., Marcombo, 2003 (in Spanish). Strain gauges, bridges and position sensors.
  • Jacob Fraden. Handbook of Modern Sensors. 5th ed., Springer, 2016. The physics and application of each family of sensors.
  • Antonio Creus Solé. Instrumentación industrial. 8th ed., Marcombo, 2010 (in Spanish). Transmitters, the 4–20 mA loop and sensors for the process industry.
Development of the topic “Sensors for automation and control” of Electronic Technology (Level 5), based on the curriculum of the UTN Electronic Engineering program, 2023 curriculum — Ordinance No. 1849 of the UTN Higher Council. Back to the Topic Map · catto.ar