Catto / Topic Map · Industrial Installations Year 6
Industrial Installations · 168 h · Topic 7 of 7

Installation project

This topic brings together everything before it into a single job: surveying, calculating, drawing, budgeting, executing and verifying a complete installation. It is the first time the work looks like a real professional commission, with a client, a deadline and a budget.

Methodology Quantity takeoff Documentation Commissioning

01The stages of the project

1Site surveyDescriptive report2Loads and circuitsLoad schedule3CalculationCalculation report4DrawingsDrawing set5Quantity takeoffBudget6ExecutionWork and log7VerificationTest protocol8HandoverAs-built1Site surveyDescriptive report2Loads and circuitsLoad schedule3CalculationCalculation report4DrawingsDrawing set5Quantity takeoffBudget6ExecutionWork and log7VerificationTest protocol8HandoverAs-builtStage 1 · Site surveydeliverable: Descriptive reportStage 2 · Loads and circuitsdeliverable: Load scheduleStage 3 · Calculationdeliverable: Calculation reportStage 4 · Drawingsdeliverable: Drawing setStage 5 · Quantity takeoffdeliverable: BudgetStage 6 · Executiondeliverable: Work and logStage 7 · Verificationdeliverable: Test protocolStage 8 · Handoverdeliverable: As-builtEach stage delivers something concrete the next one needs. Skipping one saves no time: it moves it to the site.
Figure 1. The complete path, animated. Each stage delivers something concrete that the next one needs. Skipping one does not save time: it moves it, multiplied, to the site.
StageWhat is doneWhat is delivered
1Survey and starting data: what is needed, what already exists, what the regulations and the utility company require.Descriptive report and site sketch.
2Definition of loads and circuits, with their diversity factors.Load schedule and maximum demand.
3Calculation: cross-sections by current and by voltage drop, protection, grounding.Calculation report.
4Graphic documentation: floor plan, single-line diagram, functional diagrams, switchboard details.Drawing set.
5Quantity takeoff of materials and budget for materials and labor.Takeoff sheet and budget.
6Execution: layout marking, raceways, wiring, installation of switchboards and fixtures.Completed work and progress log.
7Verification and commissioning: tests, measurements and protocol.Signed test protocol.
8As-built documentation and handover.Updated drawings and operation and maintenance manual.
As-built

During execution there are always changes: a raceway that gets moved, an outlet that gets added, a circuit that gets split. The as-built documentation records the installation as it ended up, not as it was designed. It is what makes any future intervention possible, and what is most often omitted in practice.

02The calculation, in order

The calculation is not a formula but a sequence of checks. Every conductor has to pass all three, and the largest of the resulting cross-sections is adopted.

CheckCriterion
Current-carrying capacityThe circuit current must be less than the conductor's allowable current, corrected for the installation method, grouping and ambient temperature.
Voltage dropWithin the regulatory limit at the most unfavorable point. It is what governs on long runs.
Short circuitThe conductor must withstand the fault current for as long as the protection takes to clear it, without damaging the insulation.
CoordinationThe protective device must rate between the circuit current and the conductor's allowable current, and its breaking capacity must exceed the prospective short-circuit current.
Worked example · Supplying a workshop

A workshop 45 m from the main switchboard, single-phase at 220 V, with a calculated maximum simultaneous demand of 6600 VA, that is, 30 A.

  1. By current: 30 A calls for, for a conductor in flush-mounted conduit, on the order of 6 mm².
  2. By voltage drop: with 6 mm², ΔU = 2 × 0.0172 × 45 × 30/6 = 7.7 V, or 3.5 %. It exceeds the limit.
  3. With 10 mm²: ΔU = 4.6 V, 2.1 %. It complies.
  4. Adoption: 10 mm², protected by a 32 A curve C thermal-magnetic breaker, plus an RCD. The cross-section ended up being set by the distance, not by the current.

That jump from 6 to 10 mm² looks expensive in the budget and is cheap compared with the cost of redoing a flush-mounted raceway.

The full sizing and protection criteria are in electrical installations and electrical protection; the materials, in electrical materials.

03Quantity takeoff and budget

40 %38 %12 %10 %Materials40 %Cable, conduit, boxes, switches, outlets, protection andluminaires, taken off from the drawing.Labor38 %Work hours per task. It is the item mostunderestimated, especially in existing buildings.Overheads12 %Transport, tools, insurance, office time.They exist even if they are not seen.Profit10 %What makes the work sustainable. It is stated,not hidden inside the materials.The percentages are indicative and change with the type of job, but the order of magnitude holds:visible materials are never the total, and labor usually weighs as much as they do.
Figure 2. Cost breakdown, animated. The visible materials are only one part: labor is usually the largest item, and overheads exist even if you cannot see them.
The takeoff

It is the exact count, item by item, of everything needed: meters of each cable cross-section, meters of conduit, boxes, switches, outlets, protective devices, luminaires, enclosures, hardware.

It is done on the drawing, with an explicit waste allowance —on the order of 10 % for cable and conduit— and grouped by trade item. A well-done takeoff is what avoids three trips a day to the hardware store.

The budget

Prices are added to the takeoff, along with labor, estimated in hours per task. Then come overheads, transport, tools, insurance and profit.

The validity of the budget is always stated, along with what it includes and what it does not, and the payment terms. A budget with no defined scope ends in an argument.

What is most underestimated

Labor. Chasing a wall for flush conduit, chipping, setting boxes and patching takes much more time than it seems, and in an existing installation there are always surprises. A realistic estimate is built by timing your own tasks, not by copying someone else's. The second most underestimated item is small materials: screws, wall plugs, cable ties, terminals, tape. They never appear on the drawing and they are always needed.

04Verification and commissioning

TestWhat it verifies
Visual inspectionThat what was built matches the project: cross-sections, colors, labeling, IP ratings, accessibility of boxes.
Protective conductor continuityThat the PE actually reaches every exposed conductive part and every outlet point. It is the test that reveals the most faults.
Insulation resistanceWith a megohmmeter, between live conductors and with respect to ground, with the equipment disconnected.
PolarityThat the switches break the line and not the neutral, and that the outlets have line, neutral and ground in their proper places.
RCD testActual tripping current and time, measured with an instrument.
Grounding resistanceWith an earth tester, plus verification of the electrode connection.
FunctionalThat each circuit does what the drawing says: switches on what it should, and nothing else.
The order of the first energization
  1. All protective devices open and all loads disconnected.
  2. Tests with the installation de-energized: continuity, insulation, polarity.
  3. Energize the main switchboard and check the voltages before closing anything else.
  4. Close the circuits one at a time, checking the current at each step.
  5. Connect the loads progressively and monitor voltages and heating.
  6. Test the RCDs with the complete installation in service.

Closing everything at once turns any wiring error into an arcing short circuit, with the person standing in front of the switchboard.

05The capstone project

Stage 1 · Commission and survey

Each group receives a specific commission: a workshop, a shop, a section of the school or a house. Survey dimensions, uses, expected loads and site conditions. Write the descriptive report with the starting data and the assumptions adopted.

Stage 2 · Calculation and drawings

Prepare the load schedule, calculate demand, cross-sections and protection, and draw the complete set: floor plan, single-line diagram and functional diagrams. Cross-review between groups, with written feedback: reviewing someone else's project teaches as much as doing your own.

Stage 3 · Takeoff and budget

Take off all the materials from the drawing, find real prices from local shops and estimate the labor in hours. Present the budget with its scope, validity and conditions, as it would be delivered to a client.

Stage 4 · Execution and handover

Execute a representative part on a panel or in the workshop: one complete switchboard and two or three circuits. Verify with the test protocol, correct whatever turns up and hand over the as-built documentation. Defend the project before the class, answering for every decision made.

06Common mistakes

MistakeConsequence
Starting with the drawing without a surveyThe project does not match the real site and has to be redone on site.
Calculating by current onlyOn long runs the voltage drop ends up out of compliance and the already flush-mounted conductor has to be changed.
Takeoff without waste allowanceMaterial runs out halfway through the job and work stops.
Underestimating laborThe budget does not add up and the job ends up being done at a loss.
Budget with no defined scopeAn argument is guaranteed over what was included and what was not.
Not updating the drawings during the workThe documentation is useless: the next intervention is done blind.
Energizing everything at onceA wiring error becomes an arcing short circuit in front of the operator.
Handing over without a test protocolThere is no evidence that the installation is safe, nor a reference for the future.

07Self-assessment

What is the first stage of a project and why?

The survey: understanding what is needed, what already exists and what the regulations require. Without starting data, everything calculated afterward rests on assumptions.

What three checks must a conductor pass?

Current-carrying capacity, voltage drop and short-circuit stress. The largest cross-section resulting from the three is adopted.

On a long run, which criterion usually sets the cross-section?

The voltage drop. The current-carrying capacity is met with a smaller cross-section, but the distance forces you to go up one or two sizes.

Verify 10 mm² for 30 A at 45 m, single-phase.

ΔU = 2 × 0.0172 × 45 × 30/10 = 4.6 V, that is, 2.1 % of 220 V. It complies with a comfortable margin.

What is as-built documentation?

The drawings and diagrams updated with the installation as it ended up, not as it was designed. It is what allows future work to be done without guessing.

What is the difference between a takeoff and a budget?

The takeoff is the count of materials on the drawing; the budget adds prices, labor, overheads and profit.

What percentage of waste is allowed for in cable and conduit?

On the order of 10 %. Without that allowance, material runs out halfway through the job.

Which test reveals the most faults in a new installation?

The continuity of the protective conductor to every exposed conductive part and every outlet point. It is common to find outlet points where the PE was never connected.

How is an installation energized for the first time?

With all protective devices open and the loads disconnected; it is tested de-energized, the main switchboard is energized, and only then are the circuits closed one at a time, checking at each step.

What is delivered when the job is finished?

As-built drawings, a test protocol with the measured values and an operation and maintenance manual. Without that, the work is done but it has not been handed over.

Development of the topic “Installation project” of Industrial Installations (Year 6), based on the “Curriculum Proposal – Second Cycle of the Technical-Vocational Track, Secondary Education – Electronics,” Ministry of Education of the Province of Córdoba, DGETyFP. Back to the Topic Map · catto.ar